I note that the NEMA 6-30 plug is good for 30 amp, but it appears that the model FWC400 is only 2900 watts. Therefore would you recommend a 15 amp or 20 amp 2 pole breaker?

this question was asked by Guest on Mar 18th 2014, 07:34 am

Answer and Comments

The main power box can support 30 amps (4000 watts in 220 volts setup) so we include a NEMA 6-30 plug with our 220 volts saunas. However, the FWC400 sauna itself only needs 15 amps (20 amps recommended). If you install a NEMA 6-30 outlet, the breaker has to match it and should be a 30 amps breaker. If you want to use a 20 amps breaker, you can either replace the power cord plug or run the sauna power cord to the box directly.

This comment was posted by Crystal Sauna Support on Mar 18th 2014, 10:05 am